Director |
BUILDING CODE |
|
·
Ground Snow
Load: under 5000 ft. = 0 p/sf over 5000 ft = 20 p/sf ·
Wind Speed: 90
mph (3-second gust) ·
Seismic Design
Category: C ·
Exposure: C ·
Live Load:
20lb. ·
Rainfall:
3" per hour ·
Weathering: up
to 6000 ft = Negligible Over
6000 ft – Moderate ·
Frost Line
Depth: under 5000 ft. = 0 in. Over 5000 ft. = 12 in. ·
Termite: Very
Heavy ·
Decay: None to
Slight ·
Winter Design
Temperature: 18 – 20 Degrees ·
Flood Hazards:
12/4/84, 5/19/87, 4/17/89, 2/13/00, 2/15/00, and new panels as adopted by
FEMA. For other
types of projects, the Building Safety Code consists of the 2003 editions of
the International Building Code, International
Mechanical Code, International Energy Conservation Code, International Fire
Code, International Fuel Gas Code, International Electrical Code, the 2002
National Electrical Code (NFPA 70), and the Arizona State Plumbing Code (the
1994 UPC as amended). Below is
the list of amendments and appendices adopted as the Cochise County
Building Safety Code A link to
the adopted City of http://www.ci.sierra-vista.az.us/ Including Appendices and Amendments Appendices ·
B: Board of Appeals ·
E: Supplementary Accessibility Requirements ·
G: Flood Resistant Construction ·
I: Patio Covers Amendments to the 1.
At Section 101.1 Title, change to read: "These regulations
shall be known as the Building Code of the 2.
At Section 101.4.5, delete the entire section. 3.
At Section 102.6, change to read: "….the
International Existing Building Code or the International Fire Code," 4.
At Section 103.1, change to read: "Enforcement
Agency. There exists a Building Code Division under the Cochise County
Planning Department and the official in charge thereof shall be known as the
Building Official. 5.
At Section 103.2, delete entire section. 6.
At Section 103.3, delete entire section. 7.
At Section 105.2.7, change to read: "Painting,
papering, tiling, carpeting and similar finish work." 8.
At Section
108.3 Building permit valuations (7-6-06), Change to read: The valuation
of work for Complete Structures and Additions shall be determined from the
County adopted ICC Bi-Yearly Construction
Costs Schedule or the adopted Residential
One and Two Family Homes Valuation
Rates. If a project is covered under an adopted Flat Fee rate the value
of the work is still required for reporting purposes. For Remodeling, Tenant Fit-Ups and
Phased Project work the applicant for a permit shall provide an estimated
permit value at the time of application. Permit valuations shall include
total value of work, including materials and labor, for which the permit is
being issued, such as electrical, gas, mechanical, plumbing equipment and
permanent systems. If, in the opinion of the building official, the valuation
is underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation
shall be set by the building official. 9.
At Section 109.3.7, "delete the entire section and
renumber the remaining sections 109.3.7 – 109.3.9." 10.
At Section 310.1, R-4, change to read: "Residential
occupancies shall include buildings arranged for occupancy as Residential
Care / Assisted Living Facilities including more than six but not more than
16 occupants, excluding staff"(Amended per Resolution 04-19, Docket
R-03-06). 11.
At Section 406.1.3, change the first paragraph to
read: "Carports of combustible construction and garages shall comply
with the provisions of this section for separation and opening protection.
Carport and garage floor surfaces shall be of approved noncombustible
material." 12.
At Section 406.1.4(1), change all references of
1/2"-inch gypsum board to 5/8"- inch gypsum board. At the end of
this section, insert: "Doors providing opening protection shall be
maintained tight-fitting, self-closing and self-latching. Windows are not
permitted in the separation wall. All walls supporting the fire-resistance
rated ceiling shall be protected with 5/8"-inch gypsum board." 13.
At Section 406.1.4(3), change to read: "Refer to
Section 712 for protection of other through or membrane penetrations." 14.
At Section 406.1.4, insert subsection 406.1.4(4):
"Attic access opening. The attic access opening protection supports
shall be of noncombustible material. Where a pull-down ladder in installed,
it shall be a fire-rated ladder assembly. 15.
At Section 708.1(3), change to read: "Walls
separating tenant spaces." 16.
At Section 717.1, change first sentence to read:
"In construction designated as combustible construction by the design
professional, fire blocking and draft stopping shall be installed in
concealed locations in accordance with this section." (Continue the
remainder of this paragraph). 17.
At Section 903.2.3(2), change to read: "Where a
Group F-1 fire area is located more than two stories above grade; or…" 18.
At Section 903.2.6(2), change to read: "Where a
Group M fire area is located more than two stories above grade; or…." 19.
At Section 903.2.8(2), change to read: "A Group S-1
fire area is located more than two stories above grade; or…." 20.
At Section 903.2.10.3, change to read: "Buildings
more than two stories in height. An automatic sprinkler system shall be
installed throughout every story of all buildings more than two stories or
with a floor level having an occupant load of 30 or more." (The exceptions
remain unchanged). 21.
At Section 1011.1, Revise by adding the following
sentence to the end of the first paragraph: "Floor level exit signs,
when exit signs are required, additional approved low-level exit signs which
are internally or externally or self-illuminated shall be provided in all
interior corridors serving guest rooms of hotels in Group R-1
occupancies." 22.
At Section 1011.5.3, delete the exception. 23.
At Section 1805.2, Change the first sentence to read
as follows: "The minimum depth of footings below the undisturbed ground
surface shall be 12 inches for 1000 p/sf allowable
foundation pressure and minimum 18 inches for values of Table 1804.2." 24.
At Section 2111.3, change to read: "In Seismic
Design Category C and D, masonry and concrete fireplaces shall…." and
"In Seismic Design Category A and B, reinforcement and seismic anchorage
is not required." (Requires reinforcement of masonry fireplaces and
chimneys in moderate seismic zones). 25.
At Section 2111.4, insert "C" after Seismic
Design Category. (Requires seismic anchorage of masonry fireplaces in
moderate seismic zones). 26.
At Section 2902.6, insert subsection 2902.6.4 to
read: "In existing buildings, one public / employee restroom is
permitted where the occupant load does not exceed 50." (Reduces restroom
requirements for small existing buildings). 27.
At Section 3109, delete the entire section and
insert, in lieu thereof, "the International Residential Code, 2003
edition, Appendix G, as amended shall apply." International Residential Code,
2003 edition: Appendices: ·
A: Sizing and Capacities of Gas Piping ·
B: Sizing of Venting Systems Serving Appliances Equipped with Draft
Hoods, Category I appliances and Appliances Listed for Use and Type B Vents. ·
C: Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems ·
D: Recommended Procedure or Safety Inspection of an Existing Appliance
Installation ·
G: Swimming Pools, Spas and Hot Tubs ·
H: Patio Covers ·
J: Existing Building and Structures ·
K: Sound Transmissions Amendments to the International Residential Code 1.
At Section R101.1 Title, change to read: "These
provisions shall be known as the Residential Code for One and Two-Family
Dwellings of the 2.
At Section R103.1, change to read: "Enforcement
agency. There exists a Building Code Division under the Cochise County
Planning Department and the official in charge thereof shall be known as the
Building Official. 3.
At Section R103.2, delete the entire section. 4.
At Section R103.3, delete the entire section. 5.
At Section R105.2.1, change to read: "…120 square
feet." 6.
Add - New
Section R105.2.3 Ordinary Repairs (7-6-06): Ordinary
repairs which involve only the replacement of component parts of existing
work with similar parts or materials and don't exceed $1000.00 in valuation
(materials and labor at market value), and do not change any structural,
electrical, mechanical, plumbing or fire safety condition.
A
"component part" is a portion of an assembly and not a complete
rework or replacement of the total assembly (e.g., an existing door or water
heater replaced with a new unit and a repair or replacement of individual
roof shingles but not an entire re-roof). Ordinary repairs need to abide
by the limitations contained in 'Section
R105.2.2 Repairs' of this code. 7.
At Section R105.2.6, change to read: "Painting,
papering, tiling, carpeting and similar finish work." 8.
At Section
R-108.3 Building Permit valuation (7-6-06), Change to
read: The valuation of work for Complete Structures and Additions shall be
determined from the County adopted ICC
Bi-Yearly Construction Costs Schedule or the adopted Residential One and Two
Family Homes Valuation Rates. If a project is covered under an adopted
Flat Fee rate the value of the work is still required for reporting purposes.
For Remodeling, Tenant Fit-Ups and
Phased Project work the applicant for a permit shall provide an estimated
permit value at the time of application. Permit valuations shall include
total value of work, including materials and labor, for which the permit is
being issued, such as electrical, gas, mechanical, plumbing equipment and
permanent systems. If, in the opinion of the building official, the valuation
is underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final
building permit valuation shall be set by the building official. 9.
At Table R301.2(1), insert the following data:
Ground snow load
Under 5500 ft. 0 p/sf.
Above 5500 ft. 20 p/sf.
Wind Speed 90 mph (3 - second gust)
Seismic Design Category
C
Exposure C
Live Load 20 lb.
Rainfall 3"
per hour
Weathering Negligible Above
6000 ft. Moderate
Frost Line Depth
Under 5500 ft. 0 in.
Above 5500 ft. 12 in. Termite Very
Heavy
Decay None
to Slight
Winter Design Temperature 18
– 20 Degrees
Flood Hazards 12/4/84, 5/19/87,
4/17/89,
2/13/00, 2/14/00, 2/15/00,
and new panels as adopted by FEMA 8. At Section R309, insert the words "or carport of combustible
construction", after all references to garage. (Requires fire separation
from carport). 9. At Section R309.1, insert at the end of section: "Doors
providing opening protection shall be maintained self-closing and
self-latching." (Amendments 4 and 5 require a one-hour fire protective
separation between a house and attached garage: IRC does not require
self-closing and self-latching doors, and requires ˝ inch gypsum board only). 10. At Section R309.2, change the two references of "1 / 2-inch
gypsum board" to "5 / 8-inch Type X gypsum board". 11. At Section R309.2, insert subsection "R309.2.1 Attic access
opening. The attic access opening protection supports shall be of
noncombustible material." Where a
pull-down ladder is installed, it shall be a fire-rated ladder assembly. 12. At Section R311.2.2, change the reference of "1/2 – inch
gypsum board" to "5/8 – inch Type X gypsum board." 13. At Section R313.2, insert the following after the second
sentence: "Smoke alarms shall not be installed on a dedicated circuit
and shall originate from a general-purpose branch circuit." 14. At Section R321, change to read: "…to be plainly visible and
legible, in contrasting colors, from the street…." 15. At Section R403.1.3, insert "C" after Seismic Design
Categories. (4 locations) 16. At Section R403.1.3.2, delete the exception. 17. At Section R404.1.4, Insert "C" after Seismic Design
Categories. (4 locations 18. At Section R602.10.1, second paragraph, change to read:
"….if the bracing begins more than 12.5 feet from each end."
(Changes from 12 feet). 19. At Section R606.10, change to read: "Masonry walls shall be
reinforced and anchored. 20. At Figure R606.10 (2), change the following: change #4 bars at 10
ft. o.c. to 4 ft. o.c.;
add one 1/2" bar @ top of foundation; add two 1/2" bars @ bottom of
foundation; add one 1/2" bar @ top of wall; add one 1/2" bar @ roof
connection. 21. At Section R606.11.2.2.3, end of the first paragraph, change to
read: "….and at a maximum spacing of 4 feet." (Changes rebar
requirement from 10 foot spacing). 22. At Section R1003.3, insert "C" after Seismic Design
Categories. 23. At Section R1003.4, insert "C" after Seismic Design
Categories. 24. At Section P2603.6.1, revise the paragraph to read: "Sewer
depth regardless of freezing conditions, all building sewers that connect to
private or public systems shall be a minimum of 12 inches below grade." 25. At Section P3201.2 exception, change to read: "Exception:
Traps for floor drains shall be fitted with a trap primer." 26. At Section E3501, amend by adding: Section E3501.8. Recessed
Service Entry. A recessed service entry is not permitted. 27. At Section E3501.6.2, amend by adding the following at the end of
the first paragraph: "Service disconnecting means and risers shall be
surface mounted." 28. At Section E3501.6.2, amend by changing the first sentence to
read: "The service disconnecting means shall be permanently installed on
the outside of the structure." 29. At Section E3502.1, amend the second sentence to read: "For
one-family dwellings, the rating of the ungrounded conductor shall be not
less than 200 amperes, 3-wire. Exception: Existing structures." 30. At Section E3507.3.2, delete this section. 31. At Section E3508.1, insert a second paragraph: "All
accessory structures with a poured foundation require the installation of a
concrete-encased electrode as required by Section E3508.1.2." 32. At Section E3801.2.2 subparagraph 1, delete the word
"fireplaces." 33. At Section E3801.4.5, third sentence, change to read:
"Receptacle outlets rendered not readily accessible by appliances or
appliance garages fastened in place, or appliances or appliance garages
occupying dedicated space, shall not be considered as these required
outlets." 34. At Section E3801.10, insert after the first sentence:
"Hallways and foyers 5 feet or greater in width shall have receptacle
spacing as required by Section E3801.2." 35. At Section E3802, amend by adding new section: E3802.9 Arc-Fault
Circuit Interrupter Protection. E3802.9.1 Definition. An arc-fault circuit interrupter is a device intended to provide
protection from the effects of arc faults by recognizing characteristics
unique to arcing and by functioning to de-energize the circuit when an arc
fault is detected. E3802.9.2 Dwelling Unit Sleeping Rooms. All branch
circuits that supply 125-volt, single phase, 15- and 20-ampere outlets
installed in dwelling unit sleeping rooms shall be protected by an arc-fault
circuit interrupter listed to provide protection of the entire branch
circuit. 36. At Section E3802.5, amend the first paragraph to read: "All
125-volt, single phase, 15- and 20-ampere receptacles installed in ground
level rooms and unfinished basements shall have ground-fault
circuit-interrupter protection for personnel. For purposes of this
section, ground level rooms and unfinished basements are defined as areas not
intended as habitable rooms and limited to storage areas, work areas and the
like. (The exceptions shall remain unchanged.)" 37. At Section E3903.11, amend the title to read: "Luminaries
(Fixtures) in Clothes Closets, Pantries, and Storage Rooms. (All reference in
this section to closet or clothes closet shall apply to clothes closets,
pantries, and storage rooms.)" 38. At Section E3903, amend by adding a new section: Section
E3903.11.1 Transformers. Doorbell transformers shall not be permitted in a
closet, pantry or storage room. If a receptacle is installed for an alarm
system Transformer, it shall be located above the door. 39. At Section AG105.2.1, change to read: "The top of the
barrier shall be at least 60 inches above grade…." International Mechanical Code, 2003 edition: Appendices: ·
A: Combustion Air Openings and Chimney Connector Pass-Through Amendments to the International Mechanical Code 1. At Section 101.1 Title, change to read: "These regulations
shall be known as the Mechanical Code of the 2. At Section 103.1, change to read: "Enforcement Agency. There
exists a Building Code Division under the Cochise County Planning Department
and the official in charge thereof shall be known as the Building Official. 3. At Section 103.2, delete entire section. 4. At Section 103.3, delete entire section. 5. At Section 106.5.2, delete the entire section and insert in lieu
thereof the International Building Code, 2003 edition, Section 108.2, as
amended. 6. At Section 106.5.3, delete the entire section and insert in lieu
thereof the International Building Code, 2003 edition, Section 108.2, as
amended. International Energy Conservation Code, 2003
edition: Appendices: ·
Sections and Construction Details Amendments to the International Energy Conservation Code 1. At Section 101.1 Title, change to read: "These regulations
shall be known as the Energy Conservation Code of the 2. At Section 105, delete the entire section. International Existing Building Code, 2003 edition: Appendices: ·
A: Seismic Strengthening Provisions for Un-reinforced Masonry Bearing Wall
Buildings. ·
B: Supplementary Accessibility Requirements for Existing Buildings and
Facilities. Amendments to the International
Existing Building Code 1. At Section 101.1 Title, change to read: "These regulations
shall be known as the Existing Building Code of the 2. At Section 101.4, delete reference to International Property
Maintenance code. 3. At Section 101.5, delete reference to International Property
Maintenance code. 4. At Section 103.1, change to read: "Enforcement Agency. There
exists a Building Code Division under the Cochise County Planning Department
and the official in charge hereof shall be known as the Building
Official." 5. At Section 103.2, delete entire section. 6. At Section 103.3, delete entire section. 7. At Section 105.2.2, change to read: "Painting, papering,
tiling, carpeting and similar finish work. 8. At Section 1101.2, delete reference to International Property
Maintenance code. 9. At Section 1201.3.2, delete reference to International Property
Maintenance code. International Fire Code, 2003
edition: Appendices: ·
B: Fire-Flow requirements for Buildings ·
D: Fire Apparatus Access Roads ·
E: Hazard Categories ·
F: Hazard Ranking ·
G: Cryogenic Fluids – Weight and Volume Equivalents Amendments to the International
Fire Code 1. At Section 101.1 Title, change to read: "These regulations
shall be known as the Fire Code of the 2. At Section 103.1, change to read: "Enforcement Agency. There
exists a Building Code Division under the Cochise County Planning Department
and the official in charge thereof shall be known as the Building Official.
Any code reference to Fire Code Official shall be replaced by Building
Official. 3. At Section 103.2, delete entire section. 4. At Section 103.3, delete entire section. 5. At Section 503.1.1, change to read: "Approved fire apparatus
access roads (lanes) shall be provided for every facility, building or
portion of a building hereafter constructed or moved into or within the
jurisdiction. The fire apparatus access road shall comply with the
requirements of this section and shall extend to within 150 feet (45.75 m) of
all portions of the facility.
Buildings exceeding 30 feet (9.14 m) in height and set back more than
50 feet (15.25 m) from a common access way shall also require an approved
fire access road. The marking of fire access roads on private property,
devoted to public use, shall be approved by the code official and police
department. Exception: Where buildings are protected throughout with an
approved Automatic sprinkler system, the provisions of this section shall be
permitted to be modified by the code official." 6. At Section 503.3, change to read: "Fire lanes shall be
marked with free standing signs or marked curbs, sidewalks, or other traffic
surfaces that have the words 'Fire Lane – No Parking' painted in contrasting
colors at a size and spacing approved by the authority having
jurisdiction." International Fuel Gas Code, 2003
edition: Appendices: ·
A: Sizing and Capacities of Gas Piping ·
B: Sizing of Venting Systems Serving Appliances Equipped with Draft Hoods,
Category I Appliances, and Appliances Listed for Use with Type B Vents. ·
C: Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems ·
D: Recommended Procedure for Safety Inspection of an Existing
Appliance
Installation. Amendments to the International
Fuel Gas Code 1. At Section 101.1 Title, change to read: "These regulations
shall be known as the Fuel Gas Code of the 2. At Section 103.1, change to read: "Enforcement agency. There
exists a Building Code Division under the Cochise County Planning Department
and the official in charge thereof shall be known as the Building
Official." 3. At Section 103.2, delete entire section. 4. At Section 103.3, delete entire section. 5. At Section 106.5.2, delete the entire section and insert in lieu
thereof the International Building Code, 2003 edition, Section 108.2, as
amended. 6. At Section 106.5.3, delete the entire section and insert in lieu
thereof the International Building Code, 2003 edition, Section 108.2, as
amended. 7. At Section 303.7, insert Subsection 303.7.1 to read:
"Liquefied petroleum gas piping shall not serve any gas appliance
located in a pit or basement where heavier-than-air gas might collect to form
a flammable mixture." International Electrical Code –
Administrative Provisions, 2003 edition: Appendices: ·
None Amendments to the International
Electrical Code – Administrative Provisions 1. At Section 101.1 Title, change to read: "These regulations
shall be known as The Electrical Code-Administrative Provisions of the 2. At Section 201.3, delete reference to the International Private
Sewage Disposal Code, International Property Maintenance Code and the
International Zoning Code. 3. At Section 301.1, change to read: Enforcement agency. There
exists a Building Code Division under the Cochise County Planning Department
and the official in charge thereof shall be known as the Building Official. 4. At Section 301.2, delete entire section. 5. At Section 301.3, delete entire section. 6. At Section 404.2, delete the entire section and insert, in lieu
thereof, the International Building Code, 2003 edition, Section 108.2, as
amended. NFPA 70 - National Electrical
Code, 2002 edition: Appendices: ·
None Amendments to the National
Electrical Code 1. At Article 210-8(B)(2) – amend to read: "Rooftops. The receptacle(s)
shall have the reset located on the roof." [NEC does not specify
location of reset] 2. At Article 210.8(A)(5), Amend the first paragraph to read: "All 125-volt, single phase, 15- and 20-ampere receptacles installed in ground level rooms and unfinished basements shall have ground-fault circuit-interrupter protection for personnel. For purposes of this section, ground level rooms and unfinished Basements are defi |